The economic drive
solution for applications up to 7.5 kW. X200 frequency inverters are suitable
for pump and fan applications as well as for common tasks in machine construction.
The standard "Safe Stop" function according
to EN954-1 class 3 provides additional functionality and cost effectiveness.
With the integrated EMC filter the inverter fullfills EN61800-3 standard
and is complying with standards like CE, UL, cUL, c-Tick and RoHS. |
| |
 |
- 0.2 ~ 7.5 kW
- Integrated EMC Filter
- Integrated "Emergency Stop" function
- Automatic Energy saving function
|
- RS485 Interface with Modbus RTU on board
- Network Options: Profibus, CanOpen
- RoHS Compliance
- Side-by-Side installation
- Global standards CE, UL, c-UL und c-Tick
And many more
|
| X200 |
1- / 3-phase 200 V class |
| Model number |
002
SFEF |
004
SFEF |
005
SFEF |
007
SFEF |
011
SFEF |
015
SFEF |
022
SFEF |
| Applicable motor (kW) |
0.2 |
0.4 |
0.55 |
0.7 |
1.1 |
1.5 |
2.2 |
| Rated output current (A) |
1.4 |
2.6 |
3.0 |
4.0 |
5.0 |
7.1 |
10.0 |
| Rated input voltage |
1
~ 200 … 240 V, +10 %, -15 %, 50/60 Hz ±5 % |
| Rated output voltage |
3 ~ 200 … 240 V (corresponding
to input voltage) |
| Integrated EMC filter |
EN61800-3 category C1 filter |
| Output frequency range |
0.5 … 400 Hz |
| Frequency accuracy (at 25 °C ±10 °C) |
Analogue setting: ±0.4
%, digital setting: ±0.01 % |
| Frequency setting resolution |
Analogue setting: Maximum
frequency/1000, digital setting: 0.1 Hz |
| V/f characteristics |
V/f control, V/f variable
(constant torque, reduced torque) |
| Overload capacity |
150 % for 60 s |
| Acceleration/deceleration time |
0.01 - 3000 s (linear, sigmoid),
two stage accel./decel. |
| Starting torque |
100 % at 6 Hz |
| Input |
Intelligent input terminal |
10 kOhm input impedance,
sink / source logic selectable |
| Functions |
FW(Forward), RV(Reverse),
CF1-CF4(Multispeed command), JG(Jogging), DB(External DC braking), SET(Second
motor constants setting), 2CH(Second accel./decel.), FRS(Free-run stop),
EXT(External trip), USP(Unattended start protection), SFT(Software lock),
AT(Analog input selection), RS(Reset), PTC(Thermistor input), STA(3-wire
start), STP(3-wire stop), F/R(3-wire fwd./rev.), PID(PID On/Off), PIDC(PID
reset), UP/DWN(Remote-controlled accel./decel.) , UDC(Remote-controlled
data clearing), OPE(Operator control), ADD(ADD frequency enable), F-TM(force
terminal mode), RDY(quick start enable),S-ST(Special-Set 2nd Motor Data),EMR(Safety
stop), NO(Not selected) |
| Output |
Intelligent output terminal |
27V DC 50mA max open collector
output, 1 terminals,
1c output 250V AC/30V DC 2.5A relay (AL0, AL1, AL2 terminals) |
| Functions |
RUN(run signal), FA1(Frequency
arrival type 1 - constant speed), FA2(Frequency arrival type 2 - over-frequency),
OL(overload advance notice signal), OD(Output deviation for PID control),
AL(alarm signal), DC(Wire brake detect on analog input), FBV(PID Second
Stage Output), NDC(ModBus Network Detection Signal), LOG(Logic Output Function),
ODC(Option Card Detection Signal), LOC(Low load) |
| Analogue output terminal |
0 … 10 V, analogue
frequency monitor, analogue current monitor |
| Serial port |
RS485 (Modbus RTU) |
| Standards |
CE, UL, cUL, c-Tick |
| Protection |
Overcurrent, overvoltage,
undervoltage, overload, overheat, ground fault protection at startup,
input overvoltage, external trip,
EEPROM error, CPU error, USP error, Termistor error, Driver error,
Safety stop |
| Environ-mental
conditions |
Temperature / humidity |
-10 … +50 °C (carrier
derating required for ambient temperature higher than 40 °C), no freezing
/ 20 … 90 % humidity (non condensing) |
| Vibration / lnstallation |
5.9 m/s2 10…55 Hz /
altitude 1000 m or less, indoors, no corrosive gases or dust |
| Options |
Remote operator, copy unit,
cable for digital operator, reactor for improving power factor, noise filter,
ProDrive Software |
| Protection class |
IP20 |
| Weight kg (approx.) |
0.8 |
1.0 |
1.5 |
2.4 |
2.5 |
1.5 |
2.3 |
| |
80 x
155 x
93 |
80 x
155 x
107 |
110 x
189 x
128 |
110 x
189 x
155 |
|
| X200 |
3-phase 400 V class |
| Model number |
004 HFEF |
007 HFEF |
015 HFEF |
022 HFEF |
030 HFEF |
040 HFEF |
055 HFEF |
075 HFEF |
| Applicable motor (kW) |
0.4 |
0.7 |
1.5 |
2.2 |
3.0 |
4.0 |
5.5 |
7.5 |
| Rated output current (A) |
1.5 |
2.5 |
3.8 |
5.5 |
7.8 |
8.6 |
13 |
16 |
| Rated input voltage |
3
~ 380 … 480 V, +10 %, -15 %, 50/60 Hz ±5 % |
| Rated output voltage |
3 ~ 380 … 480 V
(corresponding to input voltage) |
| Integrated EMC filter |
EN61800-3 category C2
filter |
| Output frequency range |
0.5 … 400 Hz |
| Frequency accuracy (at 25 °C ±10 °C) |
Analogue setting: ±0.4
%, digital setting: ±0.01 % |
| Frequency setting resolution |
Analogue setting: Maximum
frequency/1000, digital setting: 0.1 Hz |
| V/f characteristics |
V/f control, V/f variable
(constant torque, reduced torque) |
| Overload capacity |
150 % for 60 s |
| Acceleration/deceleration time |
0.01 - 3000 s (linear,
sigmoid), two stage accel./decel. |
| Starting torque |
100 % at 6 Hz |
| Input |
Intelligent input terminal |
10 kOhm input impedance,
sink / source logic selectable |
| Functions |
FW(Forward), RV(Reverse),
CF1-CF4(Multispeed command), JG(Jogging), DB(External DC braking),
SET(Second motor constants setting), 2CH(Second accel./decel.), FRS(Free-run
stop), EXT(External trip), USP(Unattended start protection), SFT(Software
lock), AT(Analog input selection), RS(Reset), PTC(Thermistor input),
STA(3-wire start), STP(3-wire stop), F/R(3-wire fwd./rev.), PID(PID
On/Off), PIDC(PID reset), UP/DWN(Remote-controlled accel./decel.) ,
UDC(Remote-controlled data clearing), OPE(Operator control), ADD(ADD
frequency enable), F-TM(force terminal mode), RDY(quick start enable),S-ST(Special-Set
2nd Motor Data),EMR(Safety stop), NO(Not selected) |
| Output |
Intelligent output terminal |
27V DC 50mA max open
collector output, 1 terminals, 1c output 250V AC/30V DC 2.5A relay
(AL0, AL1, AL2 terminals) |
| Functions |
RUN(run signal), FA1(Frequency
arrival type 1 - constant speed), FA2(Frequency arrival type 2 - over-frequency),
OL(overload advance notice signal), OD(Output deviation for PID control),
AL(alarm signal), DC(Wire brake detect on analog input), FBV(PID Second
Stage Output), NDC(ModBus Network Detection Signal), LOG(Logic Output
Function), ODC(Option Card Detection Signal), LOC(Low load) |
| Analogue output terminal |
0 … 10 V, analogue
frequency monitor, analogue current monitor |
| Serial port |
RS485 (Modbus RTU) |
| Standards |
CE, UL, cUL, c-Tick |
| Protection |
Overcurrent, overvoltage,
undervoltage, overload, overheat, ground fault protection at startup,
input overvoltage, external trip, EEPROM error, CPU error, USP error,
Termistor error, Driver error, Safety stop |
| Environ-mental conditions |
Temperature / humidity |
-10 … +50 °C
(carrier derating required for ambient temperature higher than 40 °C),
no freezing / 20 … 90 % humidity (non condensing) |
| Vibration / lnstallation |
5.9 m/s2 10…55
Hz / altitude 1000 m or less, indoors, no corrosive gases or dust |
| Options |
Remote operator, copy
unit, cable for digital operator, reactor for improving power factor,
noise filter, ProDrive Software |
| Protection class |
IP20 |
| Weight kg (approx.) |
1.5 |
2.3 |
2.4 |
5.5 |
5.7 |
| Dimensions W/H/D in mm |
110 x
189 x
128 |
110 x
189 x
155 |
180 x
250 x
163 |
|
* Item specifications are preliminary and are subject to change without notice
 |
 |